• Translate 58 LonWorks network variables to Modbus registers
• LonMark Ver. 3.3 Sensor & Actuator Functional Profi les
• Supports Modbus “coils”, input registers, and holding registers
• Single or double Modbus registers, signed, unsigned, IEEE 754
• All scalar LonMark SNVT types supported
• SNVT_switch & SNVT_state also supported
• SNVT types dynamically assignable via LonMaker
• Modbus register mapping dynamically mappable via LonMaker
• Modbus registers may be scaled (x10, x100, x0.1, x0.01, etc.)
• Min/max send time, send on delta confi gurable per point
• Modbus (master) polling interval confi gurable per point
• Object override supported on point by point basis
• Bidirectional communication between LonWorks and Modbus
• LonMark certifi ed, version 3.3
• 3150L Neuron® Chip, 48K Flash memory, 10K RAM
• TP/FT-10 (FTT-10A) transceiver
• Powered by 10-30VDC or 12-24VAC 50/60 Hz
• Power Consumption: 0.1A @ 24VDC
• DIN rail mounting, 100mm H x 70mm W x 60mm D
• Pluggable screw terminal block for power & LonWorks network
• Operating temperature -40°C to +85°C; Humidity 5% to 90%