• Read/Write any standard Modbus register via BACnet objects
• 300 Input objects each of types AI, BI, MSI
• 100 Output objects each of types AO, BO, MSO
• 100 Value objects each of types AV, BV, MSV
• BACnet slave is Modbus RTU master
• BACnet slave is also Modbus TCP client (master)
• Bidirectional communication between BACnet and Modbus
• Supports Modbus “coils”, input registers, holding registers
• Single or double Modbus registers, signed, unsigned, IEEE 754
• Modbus register mapping confi gured via web interface
• Modbus registers may be scaled (x10, x100, x0.1, x0.01, etc.)
• Modbus (master) polling interval confi gurable per point
• Commandable BACnet objects implement priority array
• EIA-485 transceiver for Modbus RTU
• 10/100BaseT Ethernet for BACnet IP and Modbus TCP
• Powered by 10-30VDC or 12-24VAC 50/60 Hz
• Power Consumption: 0.1A @ 24VDC
• DIN rail mounting, 100mm H x 70mm W x 60mm D
• Pluggable screw terminal block for power & RTU network
• Operating temperature -40°C to +85°C; Humidity 5% to 90%